05.
S4 Fault reset Reset when CLOSED
S5 Multi-step speed reference 1
(Master/auxiliary switch)
Auxiliary frequency reference when CLOSED.
S6 Multi-step speed reference 2 Multi-step setting 2 when CLOSED.
S7 Jog frequency reference Jog frequency when CLOSED.
SN SC Digital input common Refer to Table 2.10 for connection details.
SP Analog input signals
+V +15Vdc power supply +15Vdc power supply for analog inputs or transmitters +15Vdc
(Max. current: 20 mA) A1 Analog input or Speed Command 0 to +10